Modbus Tcp; Introduction; Configuration - ABB SM1000 User Manual

Videographic recorders
Hide thumbs Also See for SM1000:
Table of Contents

Advertisement

Videographic Recorders
SM1000 and SM2000

4 Modbus TCP

4.1 Introduction

Modbus TCP enables Modbus TCP devices to communicate via an ethernet network transferring Modbus messages via TCP/IP.
Communication with standard, serially connected, Modbus RTU devices is also possible through a Modbus TCP Gateway.
The instrument can be configured to act as either a Modbus TCP Server (Slave) or a Modbus TCP Client (Master) device on a
Modbus TCP network.
If configured as a Server, the recorder responds to Modbus queries transferred via the Modbus TCP protocol for the registers
described in Appendix B of the relevant instrument's User Guide, IM/SM1000 or IM/SM2000. The recorder can be configured for
unrestricted access or access can be restricted to a maximum of 6 Modbus TCP Clients, from defined IP addresses.
If configured as a Client, the recorder collects data from Modbus TCP Servers (or RTUs via a gateway) into its 24 Comms Analog and
24 Comms Digital Channels. Each analog and digital input can be individually configured to any register within any slave device. The
configuration allows for receipt of data in most commonly used data formats

4.2 Configuration

Fig. 4.1 Selecting Modbus TCP Configuration
Note. The Modbus TCP icon is displayed only if the instrument is fitted with the optional ethernet module.
12
SM1000 Only
Modbus TCP
SM2000 Only
4 Modbus TCP
IM/SMENET Issue 4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sm2000

Table of Contents