Remember that values of parameters set elsewhere are linked to the information on a report.
Such parameters are, for example, station and object identifiers, CT and VT ratios.
5.5

Limit counter L4UFCNT

5.5.1

Identification

Function description
Limit counter
5.5.2

Application

Limit counter (L4UFCNT) is intended for applications where positive and/or negative flanks on
a binary signal need to be counted.
The limit counter provides four independent limits to be checked against the accumulated
counted value. The four limit reach indication outputs can be utilized to initiate proceeding
actions. The output indicators remain high until the reset of the function.
It is also possible to initiate the counter from a non-zero value by resetting the function to the
wanted initial value provided as a setting.
If applicable, the counter can be set to stop or rollover to zero and continue counting after
reaching the maximum count value. The steady overflow output flag indicates the next count
after reaching the maximum count value. It is also possible to set the counter to rollover and
indicate the overflow as a pulse, which lasts up to the first count after rolling over to zero. In
this case, periodic pulses will be generated at multiple overflow of the function.
5.5.3

Setting guidelines

The parameters for Limit counter L4UFCNT are set via PCM600.
Switchgear control unit SAM600-IO
Application manual
There is a risk of flash wear out if the disturbance report triggers too often.
IEC 61850
identification
L4UFCNT
© Copyright 2017 ABB. All rights reserved
GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
GUID-41B13135-5069-4A5A-86CE-B7DBE9CFEF38 v2
GUID-5AECCDBC-7385-4D9F-940C-9D4A0E59B106 v1
GUID-DA5DA8D7-4821-4BFB-86CC-28658E376270 v2
Section 5
Monitoring
GUID-F3FB7B33-B189-4819-A1F0-8AC7762E9B7E v3