Routes; Application; Setting Guidelines - ABB Relion SAM600 Applications Manual

Switchgear control unit version 2.2
Hide thumbs Also See for Relion SAM600:
Table of Contents

Advertisement

Section 6
Ethernet-based communication
Redundancy : redundant communication is activated when the parameter is set to PRP-0 , PRP-1
or
HSR . The settings for the next access point will be hidden and PhyPortB will show the
second port information. Redundant communication is activated after a common write to IED
is done.
PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-networks. PRP-1
and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet Configuration Tool
can be used to activate the access point.
IEC16000039 V1 EN-US
Figure 10: ECT screen with Redundancy set to PRP-1 on Access point 1 and HSR Access
6.3

Routes

6.3.1

Application

Setting up a route enables communication to a device that is located in another subnetwork.
Routing is used when the destination device is not in the same subnetwork as the default
gateway.
The route specifies that when a package is sent to the destination device it should be sent
through the selected router. If no route is specified the source device will not find the
destination device.
6.3.2

Setting guidelines

Routes are configured using the Ethernet configuration tool in PCM600.
Operation for the route can be set to On / Off by checking and unchecking the check-box in the
operation column.
Gateway specifies the address of the gateway.
Destination specifies the destination.
Destination subnet mask specifies the subnetwork mask of the destination.
58
point 3
© Copyright 2017 ABB. All rights reserved
IEC16000039-1-en.vsdx
Switchgear control unit SAM600-IO
1MRK 511 445-UEN B
GUID-19616AC4-0FFD-4FF4-9198-5E33938E5ABD v1
GUID-2C4A312A-00DC-44C8-B2D9-CD0822E1C806 v1