ABB Relion REF615R Manual page 50

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

Section 5
4x Registers
DPU2000R
DPU 2000R
register
description
addr.
41159:1
Close Initiate
(Based on 43a)
41159:0
Trip Initiate
41160-411
Force physical
66
input
41167-411
Force physical
73
output
41174-411
Force logical
83
input command
41184-411
Set/Reset
95
command
registers
41189
ULOx controls
41196
Execute on
momentary
output contact
registers
41197
Password
character 1 & 2
41198
Password
character 3 & 4
41199
Spare
41200
Momentary
output contact
state mask
41201
Confirmation
momentary
output contact
state mask
41201:7
OUT6
44
REF615R
register
IEC 61850 path
addr.
41157:0
CTRL.CBCSWI1.Pos.Oper.ctlVal
41157:2
41157:3
41157:4
41214-41
LD0.SRGAPC1-2.Rs1-8.Oper.ctlVal and
223
LD0.SRGAPC3-4.Rs1-8.Oper.ctlVal
41197:0-
LD0.SPCRGGIO1.SPCSO(1to8).Oper.ctlVal
15
41198
41199
41200
41201
41207:10
LD0.XUGGIO100.SPCSO6.Oper.ctlVal
41212:10
LD0.XBUGGIO100.SPCSO6.Oper.ctlVal
1MRS240173-IB B
Comments on REF615R Modbus points
mapping
N/A in REF615R
"Open" command in
SBO-with-enhanced-security
mode.
(Relay needs to be set at Remote
mode at first).
"Cancel" command in
SBO-with-enhanced-security mode. Send
this command within 15 seconds delay after
sending the "Open" command to cancel
execute the "Open" command.
"Select" command in
SBO-with-enhanced-security mode. Send
this command within 15 seconds delay after
sending the "Open" command to confirm
execute the "Open" command.
"Open" command in
direct-with-normal-security mode.
(Relay needs to be set at Remote mode at
first).
N/A in REF615R
Check momentary output contact controls in
test mode
N/A in REF615R
Totally 2 blocks of set reset control
commands. Each block has 16 control
points.
N/A in REF615R
Password 2 for control structure 9.
This address is mapped for different points
in REF615R than in DPU2000R.
Confirmation register for control block 9.
Execute register for control bock 10.
Password 1 for control block 10.
Password 2 for control block 10.
Normal speed BIO card, need to set relay in
test mode and remote mode
High speed BIO card, need to set relay in
test mode and remote mode
DPU2000R Modbus Point List Mitigation Manual
REF615R