Operation Records - ABB Relion REF615R Manual

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

1MRS240173-IB B
DPU2000R
DPU 2000R
register addr.
description
41435
KVab/ KVan (Mag)
41436
KVbc / KVbn (Mag)
41437
KVca / KVcn (Mag)
41438
Vab / Van (Ang)
41439
Vbc / Vbn (Ang)
41440
Vca / Vcn (Ang)
41441
Pos Seq KV (Mag)
41442
Neg Seq KV (Mag)
41443
Pos Seq V (Ang)
41444
Neg Seq V (Ang)
41445
Fault Location
41446-41447
fault impedance,
real
41448-41449
breaker operate
time
41450-41451
Relay operate time
41452
Record status
5.3.2
REF615R
DPU2000R Modbus Point List Mitigation Manual
REF615R
Scale
register
Scale
addr.
100
41435
100
41453
100
100
41436
100
41454
100
100
41437
100
41455
100
1
1
1
100
41441
100
100
41442
100
1
1
10
41445
1000
41446-
1000
41448
1000
41449-
1000
41450
1000
41452
REF615R Modbus protocol only reads the fault records generated after the
device powers up.WebHMI can be used to read entire set of fault records
saved in the relay.
To find out the entire set of fault records in REF615R, please check
"Feeder Protection and Control REF615R Modbus Point List Manual" with
Document ID: 1MRS240052-IB.

Operation records

REF615R substitutes Modbus events for the operation records in DPU2000R
REF615R Modbus server only provides Modbus events generated after the
device powers up. WebHMI or ftp tool can be used to upload a complete
set of event records stored in the flash memory.
IEC 61850 path
LD0.FLTMSTA1.VoltsAB.mag.f
LD0.FLTMSTA1.VoltsA.mag.f
LD0.FLTMSTA1.VoltsBC.mag.f
LD0.FLTMSTA1.VoltsB.mag.f
LD0.FLTMSTA1.VoltsCA.mag.f
LD0.FLTMSTA1.VoltsC.mag.f
LD0.FLTMSTA1.VPsSeq.mag.f
LD0.FLTMSTA1.VNgSeq.mag.f
LD0.FLTMSTA1.FltDisKm.mag.f
LD0.FLTMSTA1.FltZ.cVal.mag.f
LD0.FLTMSTA1.OpTm.mag.f
Section 5
4x Registers
Comments on REF615R
Modbus points mapping
KVab in per unit
KVan in per unit
KVbc in per unit
KVbn in per unit
KVca in per unit
KVcn in per unit
N/A in REF615R
N/A in REF615R
N/A in REF615R
in per unit
in per unit
N/A in REF615R
N/A in REF615R
Distance to fault measured in
pu
41446-41447 mapped for
impedance magnitude, 41448
mapped for angle.
N/A in REF615R
Record status
47

Advertisement

Table of Contents
loading