Section 5

4x Registers

DPU2000R
register
DPU 2000R description
addr.
40265-266
Voltage VAN
40267
Voltage VAN Angle
40268-269
Voltage VBN
40270
Voltage VBN Angle
40271-272
Voltage VCN
40273
Voltage VCN Angle
40274-275
Voltage VAB
40276
Voltage VAB Angle
40277-278
Voltage VBC
40279
Voltage VBC Angle
40280-281
Voltage VCA
40282
Voltage VCA Angle
40283-284
kWatts A
40285-286
kWatts B
40287-288
kWatts C
40289-290
3 Phase kWatts
40291-292
kVARs A
40293-294
kVARs B
40295-296
kVARs C
40297-298
3 Phase kVARs
40299-300
kWatt Hours A
40301-302
kWatt Hours B
40303-304
kWatt Hours C
40305-306
kWatt Hours 3 Phase
(demand)
40307-308
kVAR Hours A
34
REF615R
Scale
register
Scale
addr.
1
40265-266
100
1
40267
1
1
40268-269
100
1
40270
1
1
40271-272
100
1
40273
1
1
40274-275
100
1
40276
1
1
40277-278
100
1
40279
1
1
40280-281
100
1
40282
1
1
40283-284
1
1
40285-286
1
1
40287-288
1
1
40289-290
1
1
40291-292
1
1
40293-294
1
1
40295-296
1
1
40297-298
1
1
40299-300
1
40364-365
1
1
40301-302
1
40366-367
1
1
40303-304
1
40368-369
1
1
40305-306
1
40370 -
1
371
1
40307-308
1
40372-373
1
IEC 61850 path
LD0.VMMXU1.PhV.phsA.cVal.mag.f
LD0.VMMXU1.PhV.phsA.cVal.ang.f
LD0.VMMXU1.PhV.phsB.cVal.mag.f
LD0.VMMXU1.PhV.phsB.cVal.ang.f
LD0.VMMXU1.PhV.phsC.cVal.mag.f
LD0.VMMXU1.PhV.phsC.cVal.ang.f
LD0.VMMXU1.PPV.phsAB.instCVal.mag.f
LD0.VMMXU1.PPV.phsAB.instCVal.ang.f
LD0.VMMXU1.PPV.phsBC.instCVal.mag.f
LD0.VMMXU1.PPV.phsBC.instCVal.ang.f
LD0.VMMXU1.PPV.phsCA.instCVal.mag.f
LD0.VMMXU1.PPV.phsCA.instCVal.ang.f
LD0.SPEMMXU1.W.phsA.instCVal.mag.f
LD0.SPEMMXU1.W.phsB.instCVal.mag.f
LD0.SPEMMXU1.W.phsC.instCVal.mag.f
LD0.PEMMXU1.TotW.instMag.f
LD0.SPEMMXU1.VAr.phsA.instCVal.mag.f
LD0.SPEMMXU1.VAr.phsB.instCVal.mag.f
LD0.SPEMMXU1.VAr.phsC.instCVal.mag.f
LD0.PEMMXU1.TotVAr.instMag.f
LD0.SPEMMTR1.DmdWhA.actVal
LD0.SPEMMTR1.SupWhA.actVal
LD0.SPEMMTR1.DmdWhB.actVal
LD0.SPEMMTR1.SupWhB.actVal
LD0.SPEMMTR1.DmdWhC.actVal
LD0.SPEMMTR1.SupWhC.actVal
LD0.PEMMTR1.DmdWh.actVal
LD0.PEMMTR1.SupWh.actVal
LD0.SPEMMTR1.DmdVArhA.actVal
LD0.SPEMMTR1.SupVArhA.actVal
DPU2000R Modbus Point List Mitigation Manual
1MRS240173-IB B
Comments on
REF615R Modbus
points mapping
reading per unit value
by default
reading per unit value
by default
reading per unit value
by default
reading per unit value
by default
reading per unit value
by default
reading per unit value
by default
active energy
(demand)
active energy
(supply)
active energy
(demand)
active energy
(supply)
active energy
(demand)
active energy
(supply)
active energy
(demand)
active energy
(supply)
reactive energy
(demand)
reactive energy
(supply)
REF615R