1MRS240173-IB B
DPU2000R
register
DPU2000R description
addr.
40772
Sum of fault current B
40773
sum of fault current C
40774
Over current trip counter
40775
breaker operations counter
40776
Recloser Counter 1
40777
Recloser Counter 2
40778
State 1 Reclose Counter
40779
State 2 Reclose Counter
40780
State 3 Reclose Counter
40781
State 4 Reclose Counter
40782
State 5 Reclose Counter
40771
Sum of fault current A
40772
Sum of fault current B
40773
Sum of fault current C
5.1.8
DPU2000R
register
DPU 2000R description
addr.
40897:15
Breaker is Tripping (TRIP )
40897:14
Breaker is Closing (Close )
40897:13
DPU is in ALARM (ALARM)
40897:12
Under voltage Trip
(27-1P )
40897:11
Negative Sequence
Over-current Trip (46)
40897:10
Phase Instantaneous
Over-current Trip (50P1)
40897:9
Neutral Instantaneous
Over-current Trip (50N1 )
40897:8
Phase Instantaneous
Over-current Trip (50P2)
40897:7
Neutral Instantaneous
Over-current Trip (50N2 )
REF615R
DPU2000R Modbus Point List Mitigation Manual
REF615R
Scale
register
addr.
1
1
1
1
40775
1
40776
1
40777
1
40778
1
40779
1
40780
1
40781
1
40782
1
42010
1
42012
1
42014

Physical and Logical Input / Output state Block

REF615R maps the 4x registers with packed bits in the same address locations as in
DPU2000R. The table 17 gives an example of packed bits in 40897.
Table 17:
Mitigation of Modbus physical and logical input/output state block
REF615R
register
IEC 61850 path
addr.
40897:15
LD0.TRPPTRC1.Tr.general
40897:14
LD0.MVGAPC8.Q3.stVal
40897:13
LD0.LLN0.Health.stVal
40897:12
LD0.PHPTUV1.Op.general
40897:11
LD0.NSPTOC1.Op.general
40897:10
LD0.PHHPTOC1.Op.general
40897:9
LD0.EFHPTOC3.Op.general
40897:8
LD0.PHHPTOC2.Op.general
40897:7
LD0.EFHPTOC4.Op.general
Scale
IEC61850 path
1
LD0.SSCBR1.OpCnt.stVal
1
LD0.DARREC1.FrqOpCnt.stVal
1
1
LD0.DARREC1.OpCnt1.stVal
1
LD0.DARREC1.OpCnt2.stVal
1
LD0.DARREC1.OpCnt3.stVal
1
LD0.DARREC1.OpCnt4.stVal
1
LD0.DARREC1.OpCnt5.stVal
100
LD0.SSCBR1.AccAPwrPhA.mag.f
100
LD0.SSCBR1.AccAPwrPhB.mag.f
100
LD0.SSCBR1.AccAPwrPhC.mag.f
Comments on REF615R Modbus points mapping
Configured by PCM600 tool.
Converted enum value to boolean to read
ALARM status
Section 5
4x Registers
Comments on REF615R
Modbus points mapping
Read addr. 42012 for
reference.
Read addr. 42014 for
reference.
See Section Section 7 for
example or explanation
N/A in REF615R
Can be used for Sum of fault
current A
Can be used for Sum of fault
current B
Can be used for Sum of fault
current C
41