Rms Peak Demand Current/Real, Reactive Power Values And Time Stamps Block; Table 14. Mitigation Of Modbus Mappings For Peak Demand Current/Real, Reactive Power Values And Time Stamps Blocks - ABB Relion REF615R Manual

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

1MRS240173-IB B
5.1.5
DPU2000R
register
DPU2000R description
addr.
40513
Peak Demand Current-A
40514
Peak Demand Current-A Year,
Month
40515
Peak Demand Current-A Day,
Hour
40516
Peak Demand Current-A Minute
40517
Peak Demand Current-B
40518
Peak Demand Current-B Year,
Month
40519
Peak Demand Current-B Day,
Hour
40520
Peak Demand Current-B Minute
40521
Peak Demand Current-C
40522
Peak Demand Current-C Year,
Month
40523
Peak Demand Current-C Day,
Hour
40524
Peak Demand Current-C Minute
40525
Peak Demand Current-N
40526
Peak Demand Current-N Year,
Month
40527
Peak Demand Current-N Day,
Hour
40528
Peak Demand Current-N Minute
40529
Peak Demand KWatts-A
40531
Peak Demand KWatts-A Year,
Month
40532
Peak Demand KWatts-A Day,
Hour
40533
Peak Demand KWatts-A Minute
40534
Peak Demand KWatts-B
40536
Peak Demand KWatts-B Year,
Month
40537
Peak Demand KWatts-B Day,
Hour
REF615R
DPU2000R Modbus Point List Mitigation Manual
RMS Peak Demand Current/Real, Reactive Power Values and
Time Stamps Block
REF615R maps all the registers in this block in the same way as in DPU2000R except
some scaling factor differences. Please see Section 5.1.3 on how to change the default
scaling factors.
Table 14:
Mitigation of Modbus mappings for peak demand current/real, reactive power values and time
stamps blocks
REF615R
Scale
register
addr.
1
40513
40514
40515
40516
1
40517
40518
40519
40520
1
40521
40522
40523
40524
1
40525
40526
40527
40528
1
40529
40531
40532
40533
1
40534
40536
40537
Scale
IEC61850 path
100
LD0.CMSTA1.MaxAmpsA.mag.f
LD0.CMSTA1.MaxAmpsA.t
100
LD0.CMSTA1.MaxAmpsB.mag.f
LD0.CMSTA1.MaxAmpsB.t
100
LD0.CMSTA1.MaxAmpsC.mag.f
LD0.CMSTA1.MaxAmpsC.t
100
LD0.RESCMSTA1.MaxAmps.mag.f
LD0.RESCMSTA1.MaxAmps.t
1
LD0.SPEMSTA1.MaxWPhsA.mag.f
LD0.SPEMSTA1.MaxWPhsA.t
1
LD0.SPEMSTA1.MaxWPhsB.mag.f
LD0.SPEMSTA1.MaxWPhsB.t
Section 5
4x Registers
Comments on
REF615R Modbus
points mapping
reading per unit
value by default
Year, Month
Day, Hour
Minute
reading per unit
value by default
Year, Month
Day, Hour
Minute
reading per unit
value by default
Year, Month
Day, Hour
Minute
reading per unit
value by default
Year, Month
Day, Hour
Minute
Year, Month
Day, Hour
Minute
Year, Month
Day, Hour
37