Huawei FusionModule2000 Maintenance Manual page 37

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Item
Wet film
humidifier
Table 3-7 Quarterly maintenance for the management system
Item
Battery
management
parameter settings
Issue 01 (2020-12-25)
Method
Start the
equipment,
choose Maint
> Diagnostic
Mode > Enter
on the main
screen, and
start the wet
film
humidifier.
Method
On the UPS
LCD, choose
System Info
> Settings
> Battery
Param. and
check
whether
battery
manageme
nt
parameters
are set as
required.
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Water drainage is
normal.
Expected Result
The parameters
are set based on
requirements.
3 Routine Maintenance
Troubleshooting
● If no water is
supplied, check
the cable
connection or
replace the water
inlet solenoid
valve.
● If no water is
supplied to the
wet film
humidifier, check
the cable
connection to the
water pump or
replace the
humidifier water
pump.
Troubleshooting
Set parameters
correctly.
30

Advertisement

Table of Contents
loading

Table of Contents