Routine Maintenance Checklist - Huawei FusionModule2000 Maintenance Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)

3.2 Routine Maintenance Checklist

Table 3-1 Routine maintenance checklist
Item
Check alarms.
Check the smart
cooling product
status.
Check the
power supply
and distribution
device status.
Issue 01 (2020-12-25)
Operation Guide
On the ECC800-
Pro WebUI, choose
Home > Active
Alarms and Query
> Historical
Alarms.
On the ECC800-
Pro WebUI, choose
Monitoring >
Cooling.
On the ECC800-
Pro WebUI, choose
Monitoring >
Power
Distribution.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Standard
No abnormal
record is found for
current and
historical alarms.
● The smart
cooling product
has started.
● Current
temperature:
18–27°C;
humidity: 20%–
80%.
The power supply
and distribution
device is working
properly.
Troubleshooting
For details, see the
ECC800-Pro
documents.
For details, see the
smart cooling
product
documents.
For details, see the
power supply and
power distribution
device documents.