2.1.1 Functionality and performance specifications
Table 2-2 Functionality and Performance Specifications
Item
Model
Maximum number of mountable
modules
Transfer speed
Electrical interface
Transmission protocol
Number of connectable units
Connector
Module outside dimensions
Weight
Transfer word count
Cable length
2.1.2 Support tool specification
For the use of the FL.NET module, you must set the node numbers, common memory, and
various other items with the setup tool named [S10V FL.NET SYSTEM].
For the detailed specifications for the setup tool, see "5.4 Installing and Starting up the System"
and "5.5 Operating Method."
LQE702
2 modules per LPU (Installing from the leftmost slot is not required.)
100 Mbps
IEEE 802.3-compliant (CSMA/CD-compliant)
UDP/IP, FA link protocol Ver. 2.00
Up to 254 units per network
RJ45 connector (10BASE-T/100BASE-TX)
34 (W) × 130 (H) × 100.2 (D) mm
180 g
Cyclic: 8.5k words maximum (node)
Message: 1,024 bytes maximum (node)
Twisted-pair cable: 100 m maximum/segment (category 5 or higher)
2-3
2 FL.NET MODULE
Specifications