6.3.3

Maximum number of input/output points when AnyWireASLINK master is used

1. Calculation of maximum number of input/output points
The maximum number of available input/output points is as follows when AnyWireASLINK master block is
used.
Maximum number of
input/output points
256 points
Maximum number
of points
controllable on
system
(A) : Number of input/output points of main unit
(B) : Number of input/output points of input/output
powered extension units
(C) : Number of input/output points of input/output
extension blocks
*1.
With regard to remote I/O of the AnyWireASLINK, input/output points set by the rotary switch of the
AnyWireASLINK master are assigned.
When using together with the CC-Link master, make sure that the total number of remote I/O points in
CC-Link and AnyWireASLINK master is 128 or less. For details, refer to FX
Manual.
2. Procedures for calculating number of input/output points based on example of system
configuration
For the main unit, input/output extension units/blocks and AnyWireASLINK, the number of input/output points
and the total number of points are restricted.
X000 to X027
X030 to X047
Input/output
Main unit
powered
extension unit
Y000 to Y017
Y020 to Y037
24/16=40
16/16=32
points
Number of input/output points occupied by
special function blocks (16 points)
0 points
Number of input/output points (96 points)
Number of input/output points (excluding remote I/O points on AnyWireASLINK)
+ Number of input/output occupied points
*2.
When using 27 remote I/O points (8 points
input/output points using the rotary switch of the AnyWireASLINK master.
6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
Number of input/
output points
(A)(B)(C)(D)
+
Total number of
input/output points
For details, refer to Subsection 6.3.1.
(D) : Number of remote I/O points of FX
(E) : Number of input/output points occupied by special function blocks
(F) : Number of remote I/O points assigned to AnyWireASLINK master
X050 to X067
X070 to X077
Input
Input
extension
extension
block
block
-
16/0=16
8/0=8 points
points
points
Slave
(1 point)
Up to 128 points
256 points or less in total
Number of input/output
occupied points
8
(E) units
points
+
Number of points occupied
by special function blocks
-
Special
function block
-
-
8 points
AnyWireASLINK system
Slave
Slave
(2 point)
(8 point)
96
112
128
Number of
remaining
points
Number of
remaining points
Number of AnyWireASLINK
input/output points
3 + 2 points + 1 point) shown above, assign 32 or more
6 Examination of System Configuration
AnyWireASLINK remote I/O
(F) stations
points
Remote I/O assigned to
AnyWireASLINK master
-64CL-M
2N
-128ASL-M User's
3U
-
FX
-128ASL-M
3U
-
8 points
Slave
Slave
(8 point)
(8 point)
224
256 points
Number of remote I/O
points (32 points)
*2
Up to 128 points
1
2
128
*1
3
4
5
6
7
8
9
10
75