FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
2. Lamp load
Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load.
3. Capacitive load
Capacitive loads can generate rush current 20 to 40 times the stationary current. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load. Capacitive
loads such as capacitors may be present in electronic circuit loads including inverters.
* About the maximum load specifications of the resistance load, refer to the specification for each model.
210
→ For specifications on the main unit, refer to Subsection 4.4.1.
→ For specifications on the input/output powered extension units, refer to Chapter 15.
→ For specifications on the input/output extension blocks, refer to Chapter 16.
14 Test Operation, Adjustment, Maintenance and Troubleshooting
→ For specifications on the terminal block, refer to Chapter 20.
14.4 Maintenance and Periodic Inspection