Before Starting Input Wiring; Sink And Source Input - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
10.1

Before Starting Input Wiring

10.1.1 Sink and source input

The input terminals (X) of the main unit are common to sink/source input of 24V DC internal power.
FX
Series input/output powered extension units/blocks have input terminals common to sink/source input
2N
or only for sink input.
1. Differences between the sink input circuit and the source input circuit
• Sink input [-common]
Sink input means a DC input signal with current-flow from the input (X)
terminal.
When a sensor with a transistor output is connected, NPN open
collector transistor output can be used.
• Source input [+common]
Source input means a DC input signal with current-flow into the input
(X) terminal.
When a sensor with a transistor output is connected, PNP open
collector transistor output can be used.
2. Method of switching between sink/source input
To switch the input type to sink or source input, wire the S/S terminal to the 0V or 24V (
• In the case of AC power supply type
- Sink input: [24V] terminal and [S/S] terminal are connected.
- Source input: [0V] terminal and [S/S] terminal are connected.
• In the case of DC power supply type
- Sink input: [
- Source input: [
142
→ Refer to Subsection 10.2.3 and Subsection 10.2.4 for wiring examples.
] terminal and [S/S] terminal are connected.
] terminal and [S/S] terminal are connected.
→ Refer to Subsection 10.2.5 and Subsection 10.2.6 for wiring examples.
10 Input Wiring Procedures
10.1 Before Starting Input Wiring
L
N
24V
0V
S/S
X
L
N
24V
0V
S/S
X
or
) terminal.