Output Specifications; Relay Output - Mitsubishi Electric MELSEC-F FX3G Series User Manual

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
4.4

Output Specifications

The main unit output specifications are explained below.
4.4.1

Relay output

Item
Number of output points
Connecting type
Output type
External power supply
Resistance
load
Max. load
Inductive
load
Min. load
Open circuit leakage
current
OFF ON
Response
time
ON OFF
Circuit insulation
Display of output
operation
Output circuit
configuration
*1.
Each value inside ( ) indicates the number of occupied points.
48
4 Specifications, External Dimensions and Terminal Layout (Main Units)
FX
-14MR/
3G
*1
6 points(8)
240V AC or less(250V AC or less when the unit does not comply with CE, UL or cUL standards)
The total load current of resistance loads per common terminal should be the following value.
1 output point/common terminal: 2A or less
4 output points/common terminal: 8A or less
LED on panel lights when power is applied to relay coil.
Load
DC power
supply
Fuse
Load
AC power
supply
Fuse
A common number applies to the
Relay output specifications
FX
-24MR/
FX
3G
3G
*1
16 points
10 points(16)
Removable terminal block (M3 screw)
Relay
30V DC or less
2A/point
→ For details on the common terminal for each model,
refer to the Section 4.7 Terminal Layout.
80VA
→ For the product life, refer to Subsection 14.4.3.
→ For cautions on external wiring, refer to Subsection 12.1.4.
5V DC, 2mA (reference value)
-
Approx. 10ms
Approx. 10ms
Mechanical insulation
Y
COM
Y
COM
4.4 Output Specifications
-40MR/
FX
-60MR/
3G
24 points
of [COM
].

Hide quick links: