SUN2000-(2KTL-5KTL)-L1
User Manual
Alarm ID
Alarm
Name
2036
Grid
Overfrequ
ency
2037
Grid
Underfreq
uency
2038
Unstable
Grid
Frequenc
y
Issue 01 (2020-04-17)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
Power grid exception: The
actual power grid frequency is
higher than the standard
requirement for the local power
grid.
Major
Cause ID = 1
Power grid exception: The
actual power grid frequency is
lower than the standard
requirement for the local power
grid.
Major
Cause ID = 1
Power grid exception: The
actual grid frequency change
rate does not comply with the
local power grid standard.
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
Troubleshooting
1. If the alarm occurs occasionally,
the power grid may be abnormal
temporarily. The SUN2000
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs frequently,
check whether the power grid
frequency is within the allowed
range. If no, contact the local
power operator. If yes, modify the
grid overfrequency protection
threshold through the mobile app,
SmartLogger, or NMS with the
consent of the local power
operator.
1. If the alarm occurs occasionally,
the power grid may be abnormal
temporarily. The SUN2000
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs frequently,
check whether the power grid
frequency is within the allowed
range. If no, contact the local
power operator. If yes, modify the
grid underfrequency protection
threshold through the mobile app,
SmartLogger, or NMS with the
consent of the local power
operator.
1. If the alarm occurs occasionally,
the power grid may be abnormal
temporarily. The SUN2000
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs frequently,
check whether the power grid
frequency is within the allowed
range. If no, contact the local
power operator.
81