Figure 7-7 Grid-tied point control
Table 7-1 Grid-tied point control
Parameter Name
Active
Unlimited
power
Grid
connection
with zero
power
Grid
connection
with
limited
power
(kW)
Issue 01 (2020-04-17)
Description
-
If this parameter is set to Unlimited, the output power of the
SUN2000 is not limited and the SUN2000 can connect to the power
grid at the rated power.
Closed-loop
controller
Total power indicates export limitation of the total power at the
Limitation mode
grid-tied point.
Power
Specifies the shortest interval for a single anti-backfeeding
adjustment
adjustment.
period
Power control
Specifies the dead zone for adjusting the SUN2000 output power. If
hysteresis
the power fluctuation is within the power control hysteresis, the
power is not adjusted.
Active power
Specifies the derating value of the SUN2000 active power by
output limit for
percentage. If the Smart Dongle does not detect any meter data or
fail-safe
the communication between the Smart Dongle and the SUN2000 is
disconnected, the Smart Dongle delivers the derating value of the
SUN2000 active power by percentage.
Communication
In the SUN2000 anti-backfeeding scenario, if this parameter is set to
disconnection
Enable, the SUN2000 will derate according to the active power
fail-safe
derating percentage when the communication between the SUN2000
and the Smart Dongle is disconnected for a period longer than
Communication disconnection detection time.
Communication
Specifies the time for determining the communication disconnection
disconnection
between the SUN2000 and the Dongle.
detection time
This parameter is displayed when Communication disconnection
fail-safe is set to Enable.
Closed-loop
controller
Limitation mode
Total power indicates export limitation of the total power at the
grid-tied point.
Copyright © Huawei Technologies Co., Ltd.
If multiple SUN2000s are cascaded, set this parameter to
SDongle/SmartLogger.
If there is only one SUN2000, set this parameter to Inverter.
If multiple SUN2000s are cascaded, set this parameter to
SDongle/SmartLogger.
If there is only one SUN2000, set this parameter to Inverter.
7 Man-Machine Interaction