Commissioning
4.8 Basic parameterization of the drive objects
2. Interconnect the signal source of the digital input (8 to 15).
OR
3. Proceed as follows to change the digital input into a digital output:
– Click the selector.
– Then connect the signal sink of the digital output (8 to 15).
– If you want to invert the digital output, click on this icon
4. Repeat steps 2 or 3 for all digital inputs/outputs of the required terminal.
Measuring sockets
The measuring sockets output the analog signals. Any freely interconnectable signal can be
output at any measuring socket. A measuring socket can be used, for example, to output the
actual speed value (r0063) to a measuring instrument connected to the measuring socket.
Note
Only for commissioning and service
The measuring sockets may only be used for commissioning and service purposes. The
measurements may be performed only by appropriately trained skilled personnel.
You can make the following settings:
● Activate the limitation to a characteristic.
● Interconnect signal sources.
● Parameterize a characteristic.
● Define an offset.
164
When inverted, the icon looks like this
"Drive control > Parameters > Inputs/outputs > Measuring sockets"
.
.
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0