Huawei PDU8000 Series User Manual page 67

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000 Series:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
Figure 6-1 Switching on the SPD circuit breaker
Step 2 Switch on the input power circuit breaker to power on the PDC. If the power indicator on the
front panel of the PDC lights up, the PDC is powered on properly.
Step 3 After the MDU screen starts, log in to the system as the admin or operator user (the preset
password is 000001 for both types of users), and perform operations as shown in
Issue 02 (2016-11-10)
The input power circuit breaker refers to the output circuit breaker that controls power supply from the
upstream power distribution equipment to the PDC.
If this is the initial startup, set the language, time, date, network parameters, and system
parameters by using the Settings Wizard.
If this is not the initial startup and these parameters have been set before, the system uses
the existing settings by default.
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning Guide
Figure
6-2.
60

Advertisement

Table of Contents
loading

Table of Contents