5.3.1 Moving the PDC

Context
The PDC weighs about 350 kg. Take protective measures during movement to prevent
toppling and bumping.
Procedure
Step 1 Remove the two L-shaped brackets from the front and rear of the PDC and pallet, as shown
by (1) in
Step 2 Remove the bolts from the pallet under the PDC, as shown by (2) in
Step 3 It is recommended that six people work together to move the PDC away from the pallet, as
shown by (3) and (4) in
Figure 5-1 Removing the bolts and pallet
Step 4 Adjust the PDC leveling feet to ensure that castors touch the floor, and push the PDC to its
installation position.
----End

5.3.2 Installing the PDC on a Concrete Floor

Procedure
Step 1 Determine the PDC installation position.