Huawei PDU8000 Series User Manual page 128

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000 Series:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
Table 8-2 Routine maintenance for the PDC
Maintenance
Item
Three phase
power
indicators
Surge
protection
module
Liquid crystal
display (LCD)
screen on the
PDC
Connections of
input power
cables and
output power
cables
Signs of rodent
movements in
the PDC
PDC
component
appearance
Issue 02 (2016-11-10)
Mai
Operation
nten
Guide
ance
Inter
val
Mont
Check the
hly
luminance of
the indicators.
Mont
Check the
hly
status of the
surge protection
module
indicator and
circuit breaker.
Mont
Touch the LCD
hly
screen with
your finger.
Mont
Visual
hly
observation
Mont
Visual
hly
observation
Quart
Visual
erly
observation
Copyright © Huawei Technologies Co., Ltd.
Expected
Exception Handling
Result
The three
Replace the indicator that
phase power
generates no or dim light by
indicators
referring to
are steady
an
Indicator.
on.
The surge
If the indicator of an SPD
protectio
module is red, replace the
n module
SPD module by referring
indicator
to
8.5.1 Replacing an
is green.
SPD
The
If the circuit breaker is
circuit
switched off, switch it on.
breaker is
switched
on.
The LCD
Check whether the power
screen panel
cable is properly connected,
does not
and replace the LCD screen
display
if necessary by referring to
information
8.5.7 Replacing an
properly.
The
Take measures depending on
cables are
the severity.
not
damaged.
The
terminals
are intact
and
secure
and free
from
spark
signs and
rust.
There is no
If there is a sign of rodent
sign of
movements, ask a
rodent
professional for advice.
movements
in the PDC.
The exterior
Take measures depending on
is intact.
the severity.
8 Maintenance Guide