Samsung AM JXVHGH Series Installation Manual page 99

Table of Contents

Advertisement

Optional item
Input unit
Silent mode
Main
High-head
Main
condition setting
Long-piping
condition
setting (Setting
Main
is unnecessary
if high-head
condition is set)
Energy saving
setting
Main
(A Type PBA)
Energy control
operation
Main
(B Type PBA)
Rotation defrost
Main
(HR only)
Expand
operational
temperature
Main
range for cooling
operation (HR
only)
DVM S HE_IM_DB68-05461A-08_EN.indd 99
SEG1 SEG2 SEG3 SEG4
0
0
Disabled (Factory default)
0
1
0
2
0
3
0
7
0
4
LEVEL 1 / External contact
0
5
LEVEL 2 / External contact
0
6
LEVEL 3 / External contact
0
0
Disabled (Factory default)
Level 1 of height difference
0
1
type 1 (Indoor unit is lower
Level 2 of height difference
0
8
0
2
type 1 (Indoor unit is lower
0
3
(Outdoor unit is lower than
0
0
Disabled (Factory default)
0
1
0
9
0
2
0
0
Disabled (Factory default)
1
0
0
1
0
0
0
1
1
0
0
2
0
0
Disabled (Factory default)
1
1
0
1
0
0
Disabled (Factory default)
1
2
0
1
Function of the option
Enables the silent mode for
night-time in cooling mode
(It operates automatically
LEVEL 1 / Auto
depending on the
temperature .)
LEVEL 2 / Auto
However, if the external
LEVEL 3 / Auto
contact interface module
(MIM-B14) is used, entering
the silent mode is available
with contact signal in cooling
and heating mode .
(A type PBA : this function is
used in cooling mode .)
When outdoor unit is located
40~80m above the indoor
than outdoor unit)
unit
When outdoor unit is located
over 80m above the indoor
than outdoor unit)
unit
Height difference type 2
When indoor unit is over 30 m
above the outdoor unit
indoor unit)
When equivalent length of
farthest indoor unit from
LEVEL 1
the outdoor unit is between
100~170m
When equivalent length of
LEVEL 2
farthest indoor unit from the
outdoor unit is over 170m
Energy saving mode triggers
when the room temperature
Enabled
reaches desired temperature
while operating in heating
mode .
Energy control option of
Basic (Factory default)
designated operation sequence
Energy saving
❋ Operating in energy
Power
When enabled, continuous
heating operation is possible
Enabled
but heating performance
will decrease during rotation
defrost operation
When enabled, continuous
cooling operation is possible
Enabled
even in low temperature
condition up to -15°C, but
noise of the MCU will increase
Remarks
saving mode, capacity
might decrease compared
to normal operation mode
99