Module installation
Front side
Over 100
<Case 1>
Over 100
Over 100 Over 100
Front side
Over 100
Over 100 Over 100
Front side
❇ For <Case 1> or <Case 3>
• Height of the wall on the front side should not be higher than 1500mm .
• Height of the wall on the air inlet side should not be higher than 500mm .
• Height of the wall on the side is not limited .
• If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the
exceeded distance] should be added to the service space (S1, S2) .
S1+h1/2
DVM S HE_IM_DB68-05461A-08_EN.indd 27
Over 100
Over 100
Over 100
Over 100
<Case 3>
(Unit : mm)
S2+h2/2
Over 300
Front
Over 400
Over 400
side
<Case 2>
Height of
the wall is
unlimited
27