Refrigerant pipe installation
Additional refrigerant
H/P
46 .4 kW
Ø12 .70 (5 m)
4 .5 kW
Ø12 .70 (5 m)
Ø6 .35 (5 m)
5 .6 kW
Ø12 .70 (5 m)
Ø6 .35 (10 m)
Ø9 .52 (10 m)
5 .6 kW
Ø6 .35 (15 m)
Ø9 .52 (10 m)
Ø9 .52 (10 m)
Ø9 .52 (10 m)
7 .1 kW
7 .1 kW
7 .1 kW
7 .1 kW
Refrigerant pipe installation
f Basic amount of refrigerant within the outdoor unit (kg)
X
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length .
Classification
AM080✴XVAG✴ AM100✴XVAG✴ AM120✴XVAG✴ AM140✴XVAG✴ AM160✴XVAG✴ AM180✴XVAG✴
Basic type
Classification
AM200✴XVAG✴ AM220✴XVHG✴ AM240✴XVAG✴ AM260✴XVAG✴ AM080✴XVHG✴ AM100✴XVHG✴
Basic type
Classification
AM120✴XVHG✴ AM140✴XVHG✴ AM160✴XVHG✴ AM180✴XVHG✴ AM200✴XVHG✴ AM220✴XVHG✴
Basic type
f Amount of additional refrigerant depending on the pipe size (ⓐ)
X
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length .
Size of liquid pipe
Additional amount (kg/m)
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0 .01kg per meter
regardless of the pipe size .
46
DVM S HE_IM_DB68-05461A-08_EN.indd 46
H/R
Ø9 .52
(10 m)
11 .2 kW
Ø9 .52
(15 m)
7 .1 kW
Ø9 .52 (10 m)
Ø6 .35 (5 m)
3 .6 kW
5 .5
5 .5
8 .4
8 .4
6 .5
7 .7
Ø 6.35
Ø 9.52
0 .02
0 .06
61 .6 kW (33 .6 kW + 28 .0 kW)
Ø9 .52 (1m)
Ø12 .70 (5 m)
Ø15 .88 (10 m)
Ø12 .70 (10 m)
Ø12 .70 (10 m)
MCU
Ø6 .35(15 m)
2 .8 kW
Ø6 .35(2 m)
7 .1 kW
Ø9 .52
(25 m)
Ø9 .52 (18 m)
11 .2 kW
6 .5
7 .7
14 .3
14 .3
7 .7
8 .4
Ø 12.70
Ø 15.88
Ø 19.05
0 .125
0 .18
0 .27
MCU
Ø9 .52 (10 m)
7 .1 kW
Ø9 .52 (15 m)
7 .1 kW
Ø9 .52 (18 m)
7 .1 kW
7 .7
8 .4
6 .5
6 .5
8 .4
8 .4
Ø 22.22
Ø 25.40
Ø 28.58
0 .35
0 .53
0 .65
2017-03-24 오후 1:38:21