Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch .
❇ However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to the
outdoor unit (A), apply the pipe size (A) .
Indoor unit capacity (kW)
15 .0 kW and below
Over 15 .0 kW ~ 22 .4 kW and below
Over 22 .4 kW ~ 28 .1 kW and below
Over 28 .1 kW ~ 40 .0 kW and below
Over 40 .0 kW ~ 45 .0 kW and below
Over 45 .0 kW ~ 63 .3 kW and below
Over 63 .3 kW ~ 70 .3 kW and below
Over 70 .3 kW ~ 98 .4 kW and below
Over 98 .4 kW ~ 135 .2 kW and below
Over 135 .2 kW ~ 169 .0 kW and below
Over 169 .0 kW
Note1) If Ø 25 .40 pipe is not available on site, use Ø 28 .58 pipe .
Note2) If Ø 31 .75 pipe is not available on site, use Ø 34 .92 pipe .
Note3) If Ø 38 .10 pipe is not available on site, use Ø 41 .28 pipe
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity .
Indoor unit capacity (kW)
6 .0 kW and below
7 .1 kW ~ 16 .0 kW and below
20 .0 kW ~ 23 .0 kW and below
Over 23 .0 kW
DVM S HE_IM_DB68-05461A-08_EN.indd 39
Branch pipe length within 45m
Liquid pipe (mm)
Gas pipe (mm)
Ø 15 .88
Ø 9 .52
Ø 19 .05
Ø 22 .22
Ø 12 .70
Ø 28 .58
Ø 15 .88
Ø 34 .92
Ø 19 .05
Ø 41 .28
Ø 22 .22
Ø 53 .98
Pipe size (O.D. mm)
Liquid pipe
Ø 6 .35
Ø 9 .52
Ø 9 .52
Ø 9 .52
Branch pipe length between 45~90m
Liquid pipe (mm)
Gas pipe (mm)
Ø 19 .05
Ø 12 .70
Ø 22 .22
Ø 25 .40
Ø 28 .58
Ø 15 .88
Ø 31 .75
Ø 19 .05
Ø 38 .10
Ø 22 .22
Ø 41 .28
Ø 53 .98
Ø 25 .40
note1)
Gas pipe
Ø 12 .70
Ø 15 .88
Ø 19 .05
Ø 22 .22
2017-03-24 오후 1:38:20
note1)
note2)
note3)
39