Electrical wiring work
High EER module (Heat recovery)
Model
AM240JXVHGR1
AM260JXVHGR1
AM280JXVHGR1
AM300JXVHGR1
AM320JXVHGR1
AM340JXVHGR1
AM360JXVHGR1
AM380JXVHGR1
AM400JXVHGR1
AM420JXVHGR1
AM440JXVHGR1
AM460JXVHGR1
AM480JXVHGR1
AM500JXVHGR1
AM520JXVHGR1
AM540JXVHGR1
AM560JXVHGR1
AM580JXVHGR1
AM600JXVHGR1
AM620JXVHGR1
AM640JXVHGR1
AM660JXVHGR1
AM680JXVHGR1
AM700JXVHGR1
AM720JXVHGR1
AM740JXVHGR1
AM760JXVHGR1
AM780JXVHGR1
AM800JXVHGR1
❇ When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit
❇
capacity . (Refer to the table for each model)
❇ Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
❇
flexible cord . (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Ex .) AM500✴XVA✴✴
AM220✴XVA✴✴
ELCB
or
MCCB+ ELB
①
72
DVM S HE_IM_DB68-05461A-08_EN.indd 72
MCA
50 .0
50 .0
57 .0
64 .1
67 .5
69 .5
69 .5
76 .5
85 .0
87 .0
89 .0
94 .5
94 .5
101 .5
108 .6
112 .0
114 .0
114 .0
121 .0
129 .5
131 .5
133 .5
139 .0
139 .0
146 .0
153 .1
156 .5
158 .5
158 .5
AM160✴XVA✴✴
AM120✴XVA✴✴
②
③
MFA
63
63
63
75
75
80
80
90
100
100
100
125
125
125
125
125
125
125
150
150
150
150
175
175
175
175
175
175
175
AM500✴XVA✴✴ : 35 mm
①
2
AM280✴XVA✴✴ : 16 mm
②
2
AM120✴XVA✴✴ : 4 mm
③
2