Setting the MCU and Pipe Addresses (for HR Only)
Setting the Pipe Addresses Manually
You can use the wired or wireless remote control or the S-NET Pro 2 to set the pipe addresses for each indoor unit .
Setting by using the wired or wireless remote control (For how to operate the remote control
buttons, see the remote control user manual.)
1 . Turn on both the indoor unit and the remote control .
2 . Enter the "Option setting mode" on the remote control .
3 . Set the address of each MCU port that is connected to an indoor unit by referring to the following table . (You can
also set the address of each indoor unit .)
Option
SEG1
Value
0
Option
SEG7
Value
1
Option
SEG13
Value
2
Option
SEG19
Value
3
Examples> If the indoor unit whose address is not yet set is connected to port A on the MCU 1, set 0A0000-100000-
20101A-300000 .
If the indoor unit whose address is set to 9 is connected to port B on the MCU 2, set 0A1009-100000-
20102B-300000 .
Setting by using S-NET Pro 2
f Set the pipe addresses by using Add-on > Change address on S-NET Pro 2 . (For more information, see the S-NET
X
Pro 2 Help .)
106
DVM S HE_IM_DB68-05461A-08_EN.indd 106
SEG2
SEG3
0: The address of the indoor
unit will not be set .
A: Address setting
mode
1: The address of the indoor
unit will be set .
SEG8
SEG9
0: The RMC address will not
be set .
0
1: The RMC address will
be set .
SEG14
SEG15
0: The MCU address will
not be set .
0
1: The MCU address will
be set .
SEG20
SEG21
0
0
SEG4
SEG5
0 to 9: Hundreds
0 to 9: Tens digit
digit of the indoor
of the indoor unit
unit address
address
SEG10
SEG11
0 to F: RMC group
0
channel
SEG16
SEG17
0 to 1: Tens digit of
0 to 9: Units digit of
the MCU address
the MCU address
SEG22
SEG23
0
0
SEG6
0 to 9: Units digit
of the indoor unit
address
SEG12
0 to F: RMC group
address
SEG18
A to F: MCU port
address
SEG24
0