Fire Alarm Bell Fault - Huawei IDS1000 User Manual

Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual

6.5 Fire Alarm Bell Fault

Possible Causes
Tools and Materials
Procedure
Step 1 Check whether the power supply to the fire alarm bell is abnormal.
Trigger a smoke alarm and a temperature alarm when the cable is removed from the solenoid
valve, and observe whether the fire alarm bell rings. Use a multimeter to measure the two
terminals of the alarm bell, and check whether the voltage is within normal range.
Y => Go to
N => Regulate the voltage to a normal value.
Check whether the fault is rectified.
Step 2 Replace the fire alarm bell.
Check whether the fault is rectified.
Step 3 Check the connection between the fire alarm bell and the controller.
Use a multimeter to check whether there is any short circuit or open circuit.
Y => Rectify the connection fault.
Check whether the fault is rectified.
N => Contact Huawei technical support.
----End
Issue 01 (2014-3-15)
The power supply to the fire alarm bell is abnormal.
The fire alarm bell is faulty.
The cable connection of the fire alarm bell is abnormal.
Multimeter
Gloves
Step ladder
Screwdriver
Step
2.
If yes, no further action is required.
If no, go to
Step
2.
If yes, no further action is required.
If no, go to
Step
3.
If yes, no further action is required.
If no, contact Huawei technical support.