Components - Huawei IDS1000 User Manual

Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual

1.2 Components

Gas Extinguishing Controller
A gas extinguishing controller provides the following functions:
Table 1-2
Table 1-2 Specifications for the gas extinguishing controller
Item
AC input frequency
AC input voltage
DC backup
power
Capacity
Wire system of the detector loop
Length of the detector loop
Relay contact capacity
Issue 01 (2014-3-15)
Each core component in the fire extinguishing system can be flexibly matched with each
other to create a system that meets the fire extinguishing requirements of different levels
in a single container or combined containers.
Detects and reports composite fire alarm signals in dual loops. It can be connected to the
emergency startup button, which ensures that the system operation is under control in
case of an emergency or during onsite equipment maintenance.
Restarts automatically after a fault is rectified.
Provides a port for the gas release confirmation signal (reporting pressure values).
Generates single and composite fire alarms, drives gas release indicators and audible and
visual alarms, and controls alarm bells.
Provides an independent output port for the solenoid valve driver and supports 3 A, 24 V
solenoid valve (electric detonator) startup current.
Detects the open circuit fault of the input loop and the short circuit and open circuit of
the output loop (in active output mode).
Provides the intelligent monitoring, and overcharge and overdischarge protection for
standby batteries.
Adopts the low-power consumption design, and supports at least 48-hour consecutive
operation for the backup power.
Provides password lock protection for the keypad to prevent misoperations.
lists the specifications for the gas extinguishing controller.
Voltage
Electricity
Number of detector
loops
Number of detectors
connected to each loop
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Configuration Description
Specifications
≤ 120 W
220 V AC ± 20%
24 V DC
7.0 Ah
Two loops: one loop connected to the common
heat detector and the other connected to the
smoke detector
≤ 20 (common detectors)
Two-wire system
≤ 1000 m
7 A, 24 V DC for all relays
4