Alarm Reference - Huawei IDS1000 User Manual

Container data center single-zone fire extinguishing system
Table of Contents

Advertisement

IDS1000 Container Data Center
User Manual
Alarm
Gas
extinguish
ing
controller
communic
ation
failure
Fire
extinguish
ing
hardware
fault
Fire
extinguish
ing
triggered
Issue 01 (2014-3-15)
Alarm
Alarm
Impact on the
Severit
Type
System
y
Critical
Event
The fire
extinguishing
system cannot
be monitored.
The fire
Critical
Event
extinguishing
system does not
work.
Critical
Alarm
The fire
extinguishing
equipment has
released
extinguishing
agents into the
protected zone
of the container.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5

Alarm Reference

Solution
See the documents delivered with the
gas extinguishing controller.
1. Check whether the fire
extinguishing components are in
good condition and properly
connected.
If yes, contact Huawei
technical support.
If no, go to 2.
2. Rectify the fault and check
whether the alarm is cleared.
If yes, no further action is
required.
If no, contact Huawei technical
support.
Check whether a fire is present in the
container.
If yes, fire extinguishing cylinders are
triggered. Wait for the fire
extinguishing system to respond.
If no, check whether fire
extinguishing cylinders are triggered.
If the fire extinguishing cylinders
are triggered, press the shutdown
button on the emergency
startup/abort switch to stop fire
5 Alarm Reference
34

Advertisement

Table of Contents
loading

Table of Contents