Starting The Drive From Remote; Starting The Drive Locally - ABB ACS580MV Hardware Manual

200 kw to 6300 kw, 6 kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

96 Operation
When the drive is put into service after it has been commissioned, or after it has been
taken out of service for maintenance or troubleshooting, check the drive according to the
following list:
Check that no tools and foreign objects are left inside the cabinets.
Check that all auxiliary power supplies from external sources are switched on.
Check that all internal circuit breakers of the drive are closed.
Check that all grounding devices are removed
Check that all covers are mounted and the doors are closed, locked and / or bolted.
Check that the MCB is in operating position.
Check that there is no run interlock active.

Starting the drive from remote

When the drive is operated from remote through a higher-level control system or an
operator control desk, follow the instructions in the appropriate manuals.

Starting the drive locally

5. Press the SUPPLY ON pushbutton to connect the drive to the main power supply. The
following takes place:
The MCB closes.
The DC link charges.
While the DC link charges, the SUPPLY ON pushbutton flashes. As soon as the DC
link is charged, the SUPPLY ON pushbutton changes to a permanent light.