http://www.RSPSupply.com/p-8457-MDS-UP-9790X.aspx
When the radio is in CTS Key mode, the timer specifies how long to
wait after asserting the CTS before sending data from the
port. A timer value of zero means that data will be sent from the
FACE
data port without imposing a keying delay. Other delays may be present,
depending on how other operating parameters are configured.
Should you experience problems with repeater operation after changing
the
,
or
values, contact GE MDS.
CTS
PTT
SCD

DATAKEY [ON/OFF]

This command displays or sets the keying mode. In key-on-data mode,
the radio automatically keys itself whenever input data arrives on the
DB25 port. In key-on-RTS mode, the radio only keys in response to an
RTS or PTT signal (or the
Entering the
command alone shows whether the keying mode
DATAKEY
is key-on-data (
) or key-on-RTS (
ON
mand followed by a parameter controls whether or not the radio will
automatically key on receipt of data. The default mode is key-on-data
(
).
ON
NOTE: Key-on-data mode is only applicable when the input data
source is digital. When the input data source is analog, the
setting is irrelevant.
DATAKEY

DATE [mmm dd yyyy]

This command sets or displays the date. The accuracy of the date and
time are important, because event codes are "stamped" with the date and
time (refer to
"TIME [hh:mm:ss]" on Page
Enter the command without any parameters to display the date. Enter the
command in any of the following formats to reset the date:
DATE mmm dd yyyy
DATE mm-dd-yyyy
DATE mm/dd/yyyy
where mmm is a three-character abbreviation of the month:
Jan, Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec
dd is a two-digit number from 01 to 31 representing the day, and yyyy is
the year.
MDS 4790/9790 Series I/O Guide
Key On Data
A
B
command).
KEY
). Entering the
OFF
Set Date