68 Fault tracing
The four-digit code number in parenthesis after the fault is for the fieldbus communication.
See chapters Fieldbus control with embedded fieldbus and Fieldbus control with fieldbus
adapter in ACS355 User's manual (3AUA0000066143[English]).

How to reset

During a fault condition, you can reset the inverter by pressing the keypad key
control panel) or
switching off the supply voltage for a while. The source for the fault reset signal is selected
by parameter 1604 FAULT RESET SEL. You can restart the motor after the fault is
removed.

Fault history

The fault history stores all the detected faults. The latest faults are stored together with the
time stamp.
Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS
FAULT 2 store the most recent faults. Parameters 0401...0409 show the inverter operation
data at the time the latest fault occurred. The assistant control panel provides additional
information about the fault history.
For more information, see section Fault logger mode in ACS355 User's manual
(3AUA0000066143[English]).

Fault messages

The following faults messages are generated by the solar pump inverter.
Code
Fault
210
DRY RUN
216
PV MAX VOLT
(assistant control panel) through digital input or fieldbus or by
Cause
The inverter consumes less
current than the current set in
6016 MIN LOAD
This condition occurs when
there is no water flowing in the
pump.
The DC bus voltage in the
inverter is above the voltage set
in
6005 PV CELL MAX
• Check the availability of water
at the pump inlet.
CURRENT.
• Check for any blockage in the
pump.
• Check the number of PV cells
connected in series.
VOLT.
• Ensure that voltage is less
than the voltage set in
PV CELL MAX
Maximum allowed voltage:
• 400 V unit: 800 V
• 200 V unit: 400 V
(basic
What to do
6005
VOLT.