All parameters
No.
Name/
Value
0...3276.0 kW
6102
PQ CURVE P2
0...3276.0 kW
6103
PQ CURVE P3
0...3276.0 kW
6104
PQ CURVE P4
0...3276.0 kW
6105
PQ CURVE P5
0...3276.0 kW
6111
PQ CURVE Q1
0...3276.0 m³/h
6112
PQ CURVE Q2
0...3276.0 m³/h
6113
PQ CURVE Q3
0...3276.0 m³/h
6114
PQ CURVE Q4
0...3276.0 m³/h
6115
PQ CURVE Q5
0...3276.0 m³/h
6121
PUMP
EFFICIENCY
0...100%
6122
PUMP NOM
SPEED
0...3000 rpm
6123
CALC LOW
SPEED
100...3000 rpm
Description
Power
Defines the input power of pump at point 2 on the PQ
curve.
Power
Defines the input power of pump at point 3 on the PQ
curve.
Power
Defines the input power of pump at point 4 on the PQ
curve.
Power
Defines the input power of pump at point 5 on the PQ
curve.
Power
Defines the flow rate at point 1 on the PQ curve.
Flow rate
Defines the flow rate at point 2 on the PQ curve.
Flow rate
Defines the flow rate at point 3 on the PQ curve.
Flow rate
Defines the flow rate at point 4 on the PQ curve.
Flow rate
Defines the flow rate at point 5 on the PQ curve.
Flow rate
Defines the total efficiency of the motor/pump
combination.
Percentage
Defines the nominal speed of pump. This value is used
for flow calculation in
page 37.
Speed
Defines the minimum speed limit below which flow is
not calculated.
Speed
Actual signals and parameters 59
CALCULATED
FLOW, see
Def/ FbEq
0
10 = 1 kW
0
10 = 1 kW
0
10 = 1 kW
0
10 = 1 kW
0
10 = 1 m³/h
0
10 = 1 m³/h
0
10 = 1 m³/h
0
10 = 1 m³/h
0
10 = 1 m³/h
0
1 = 1%
100%
1 = 1 rpm
3000 rpm
1 = 1 rpm
500 rpm