ABB ACS355 Manual page 39

Solar pump inverter (+n827)
Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

Actual signals
No.
Name/Value
Bit Name
11
SUPPLY_ PHASE
12
MOTOR_STALL
13
OVERCURRENT
14
EXT_FAULT1
15
START_DELAY_
ACTIVE
0311
SOLAR STS WORD2
Bit
Name
0
EXT_FAULT2
1
AI1_LOSS
2
AI2_LOSS
3
PANEL_LOSS
4
DEV_OVERTEMP
5
ID_RUN_FAIL
6
OUTP_WIRING
Description
Value Status
1
Intermediate circuit DC voltage is oscillating due to
missing input power line phase or blown fuse.
0
No oscillation of intermediate circuit DC voltage.
1
Motor is operating in stall region due to excessive load
or insufficient motor power.
0
Motor is not operating in stall region.
1
Output current exceeds the trip level.
0
Output current is within limits.
1
External fault 1.
0
No external fault 1.
1
Start delay alarm is active.
0
Start delay alarm is not active.
A 16-bit data word.
Value Status
1
External fault 2.
0
No external fault 2.
1
Analog input AI1 signal is below the limit defined in
parameter 3021 AI1 FAULT LIMIT (See ACS355
User's manual (3AUA0000066143 [English])).
0
Analog input AI1 signal is within the limits defined
in parameter 3021 AI1 FAULT LIMIT.
1
Analog input AI2 signal is below the limit defined in
parameter 3022 AI2 FAULT LIMIT (See ACS355
User's manual (3AUA0000066143 [English])).
0
Analog input AI2 signal is within the limit defined in
parameter 3022 AI2 FAULT LIMIT.
1
Control panel selected as active control location for
drive has stopped communicating.
0
No panel loss.
1
Drive IGBT temperature is excessive.
0
Drive IGBT temperature is within limit.
1
Motor ID run is not completed successfully.
0
Motor ID run is completed successfully.
1
Incorrect input power and motor cable connection.
0
Correct input power and motor cable connection.
Actual signals and parameters 39
FbEq
1 = 1