All parameters
No.
Name/
Value
DI5
DI5,4
SOLAR
1003
DIRECTION
FORWARD
REVERSE
REQUEST
11 REFERENCE
SELECT
1102
EXT1/EXT2
SEL
EXT1
DI1
DI2
DI3
DI4
Description
Start and stop through digital input DI5.
0 = stop, 1 = start.
Direction fixes based on parameter
(REQUEST = FORWARD).
Start and stop through digital input DI5.
0 = stop, 1 = start.
Direction control through DI4.
0 = forward, 1 = reverse.
To control direction, set the parameter
DIRECTION
= REQUEST.
Solar mode.
If
6001 AUTO/MANUAL SEL
• Auto [0]—inverter starts only when the DC bus
voltage is greater than the value in
VOLT
• Manual [1]—inverter starts at the rising edge of the
parameter as set in
provided the DC bus voltage is greater than
START DC VOLT
Controls or fixes the rotational direction of the motor.
Fixed to forward
Fixed to reverse
Allows rotational direction control
Defines panel reference types, external control
location selection and external reference sources and
limits.
Defines the source from which the drive reads the
signal that selects between the two external control
locations, EXT1 or EXT2.
Note: Only EXT1 is applicable for solar pump inverter.
EXT1 active. The control signal sources are defined by
parameters
1001 EXT1 COMMANDS
SELECT.
Digital input DI1.
0 = EXT1, 1 = EXT2.
See selection DI1.
See selection DI1.
See selection DI1.
Actual signals and parameters 43
1003 DIRECTION
1003
is set as
6003 START DC
6002 MANUAL START
and
1103 REF1
Def/ FbEq
20
21
37
CMD,
6003
REQUEST
1
2
3
EXT1
0
1
2
3
4

Hide quick links: