Figure 3-6: Typical Rtd Installation - ABB XRC G5 User Manual

Hide thumbs Also See for XRC G5:
Table of Contents

Advertisement

WARNING: Bodily injury. Install electrical wiring according to requirements for the area
classification. Refer to the certification drawing indicated on the device's name tag, and national
and local codes.
IMPORTANT NOTE: This procedure applies to the XFC
support for RTD inputs.
Materials:
 RTD probe with cable and cable gland installed (probe and cable length determined by
technician)
 Nylon tie wraps
Install the RTD probe:
Insert the RTD probe into the thermowell to determine the depth setting for the probe
spring.

Figure 3-6: Typical RTD installation

Use snap-ring pliers to adjust the retaining ring below the spring on the probe. Probe depth
should be set so it is spring-loaded against the bottom of the thermowell.
Figure 3-7: RTD probe connector
Legend: RTD Probe Connector
1
SHLD (Drain wire= Green wire)
2
OUT (White wire)
3
(+) (White wire)
4
(-) (Black wire)
5
IN (Black wire)
6
Cable gland
7
Cord sealing nut
3 6 | XSE RI ES G5 | 2 10 6 02 6MNAA
G5
only. The XRC
8
Cable
9
Retaining ring
10
RTD probe
11
Spring
12
Probe connector
13
Nylon sealing ring
14
Cable nut
G5
does not have onboard