Click Send.
Click the Calibrate icon on the PCCU toolbar (the Calibrate icon shows tools).
Click I/O Interface on the navigation tree.
Repeat the calibration procedure in section
mode
XSeriesG5
proceeding with the calibration or restoring power to the device, make sure
correct AI mode.
To set the AI input signal mode:
Locate the AIs (XFC: J8, XRC: J23).
Figure 11-4: XRCG5 AIs
Figure 11-5: XRCG5 AIs and mode selector jumpers (default setting)
To set the AI to voltage mode:
If calibrating on the XFC: AIs support voltage mode by default. Ensure that there are no
external resistors connected across the AI pins.
If calibrating on the XRC: Verify that the mode selector jumper (J21, J22, J24, J25 or J26)
is across pins 2 and 3 for the selected AI.
To set the AI to current mode:
If calibrating on the XFC: Insert a precision resistor across the selected AI pins.
If calibrating on the XRC: Place the mode selector jumper (J21, J22, J24, J25 or J26)
across pins 1 and 2 for the selected AI.
Analog input calibration (voltage mode), and section
(current
mode).
Repeat the steps in section
1 3 8 | XSE RIE S G5 | 2 10 60 2 6MNAA
devices support voltage or current input signals from external devices. Before
11.5.5 Verify analog input
11.5.2 Set the AI to the correct input signal
11.5.4 Analog input calibration
calibration.
you set the