C U S T O M A P P L I C AT I O N E D I T O R M A N U A L

What is new in this version

Library versions
Each UMC version got additional expansion modules and new function blocks. The library version setting for UMC100.3 is
version 3.0, which includes all function blocks from former versions. All versions are upwards compatible to newer UMC100
releases.
The version number is stored together with the logic.
V1.0
V2.0
V3.0
For UMC100.3 generally V3.0 should be selected as shown

Backward compatibility

The new UMC100.3 can execute applications created with the previous library version V1.0 and V2.0 without any changes.
With the latest custom application editor you can still create applications for previous UMC versions.
If you import existing applications created with the function block library version 1.0 or 2.0 the library selector is set to 1.0 or
2.0 automatically. If you want to use new function blocks in your application change the library version to 3.0 now and add
the new function blocks. This application can not be used in an UMC R0100xR020x anymore but only in the new UMC100.3.

Consideration on parameter I/O data profile

With the parameter "I/O data profile" it is possible to change the length of the cyclically transmitted I/O data.
In case this parameter is set to "Profile 2", the data of the following function blocks are not sent to or received from the bus:
• Analog command 0
• Binary command 2/3
• Binary monitoring 2/3/4/5
• Analog monitoring 1/2/3/4
It is not necessary to delete these blocks from a diagram.
UMC100-FBP.0
UMC100-FBP.0
UMC100.3
1SAJ520000R0100, 1SAJ520000R0200
1SAJ520000R0101, 1SAJ520000R0201
all versions