Mitsubishi Electric AE-200A Instruction Book page 46

Air conditioning control system, bacnet function
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Object
Filter Sign
[Circulating Water
Exchange Sign]
Filter Sign Reset
[Circulating Water
Exchange Sign Reset]
Prohibition On Off
*1
Prohibition Mode
Prohibition Filter Sign
Reset
[Prohibition Circulating
Water Exchange Sign
Reset]
Prohibition Set
Temperature
Prohibition Fan Speed
M-NET Communication
State
WT07919X04
Object ID
INACTIVE(0): OFF
BI_01xx11
ACTIVE(1): ON
INACTIVE(0): Reset
BV_01xx12
ACTIVE(1): Void
INACTIVE(0): Permit
BV_01xx13
ACTIVE(1): Prohibit
INACTIVE(0): Permit
BV_01xx14
ACTIVE(1): Prohibit
INACTIVE(0): Permit
BV_01xx15
ACTIVE(1): Prohibit
INACTIVE(0): Permit
BV_01xx16
ACTIVE(1): Prohibit
INACTIVE(0): Permit
BV_01xx17
ACTIVE(1): Prohibit
INACTIVE(0): Normal
BI_01xx20
ACTIVE(1): Error
Status
(1) Issue the filter sign (circulating water
exchange sign) for a specific group.
(2) In the building management system, check
to see that the filter sign (circulating water
exchange sign) for the relevant group has
been updated to "ON" (ACTIVE).
(1) From the building management system,
carry out operations for filter sign reset
(circulating water exchange sign reset)
for the group which has detected ("ON"
(ACTIVE)) filter sign (circulating water
exchange sign).
(2) In the building management system, check
to see that filter sign (circulating water
exchange sign) of the relevant group has
been updated to "OFF" (INACTIVE).
(1) From the building management system,
carry out prohibition operation for remote
controller operation (run/stop) for a specific
group.
(2) Check to see that run/stop operations have
been prohibited by the remote controller in
the relevant group.
(3) From the building management system,
carry out permission operation for remote
controller operation (run/stop) for a specific
group.
(4) Check to see that run/stop operations have
been permitted by the remote controller in
the relevant group.
• Although the operating target is an
operational mode, the checking method is
the same as "Prohibition On Off" above.
• Although the operating target is resetting filter
sign (circulating water exchange sign), the
checking method is the same as "Prohibition
On Off" above.
• Although the operating target is a set
temperature, the checking method is the
same as "Prohibition On Off" above.
• Although the operating target is a fan
speed, the checking method is the same as
"Prohibition On Off" above.
(1) Remove the M-NET transmission line which
is connected to the AE-200/AE-50/EW-50.
*3
(2) In the building management system, check
to see that the M-NET communication
status of all groups has been updated to
"Error" (ACTIVE).
(3) Connect the M-NET transmission line to the
AE-200/AE-50/EW-50.
(4) In the building management system, check
to see that the M-NET communication state
for all groups has been updated to "Normal"
(INACTIVE).
(Other errors occur when there is a
communication error, however, in this
checking step, attention should be focused
on the M-NET communication state).
46