Mitsubishi Electric AE-200A Instruction Book page 43

Air conditioning control system, bacnet function
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Method of carrying out trial runs for air conditioning control system (AE-200/AE-50/EW-50)
®
BACnet
function
Check the objects used in the system.
Refer to the table in section 5-2-1 "Instance number for basic functions" as to whether or not objects can be
supported by different unit types.
Object
On Off Setup
*1
On Off State
Alarm Signal
Error Code
Operational Mode Setup
WT07919X04
Object ID
INACTIVE(0): OFF
BO_01xx01
ACTIVE(1): ON
INACTIVE(0): OFF
BI_01xx02
ACTIVE(1): ON
INACTIVE(0): Normal
BI_01xx03
ACTIVE(1): Error
01: Normal
02: Other errors
03: Refrigeration system
fault
04: Water system error
MI_01xx04
05: Air system error
06: Electronic system
error
07: Sensor fault
08: Communication error
09: System error
01: Cool
02: Heat
03: Fan
MO_01xx05
04: Auto
05: Dry
06: Setback
Status
(1) From the building management system,
operate run/stop for a specific group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the run/stop
state of the relevant group is updated to an
operating state.
(1) Using AE-200/AE-50/EW-50 or the remote
controller, operate run/stop of a specific
group.
(2) In the building management system, check
to see that the state of run/stop of the
relevant group is updated to the operating
state.
(1) Cause air conditioning unit of a specific
group to generate an error.
(2) In the building management system,
check to see that the alarm signal of the
relevant group has been updated to "Error"
(ACTIVE).
(3) Return from an error in an air conditioning
unit of a specific group.
(4) In the building management system, check
to see that the alarm signal of the relevant
group has been updated to "Normal"
(INACTIVE).
(1) Remove the M-NET transmission line which
is connected to the AE-200/AE-50/EW-50.
*3
(2) In the building management system, check
to see that error codes for all groups have
been updated to "Communication error"
(08).
(3) Connect the M-NET transmission line to the
AE-200/AE-50/EW-50.
(4) In the building management system, check
to see that error codes for all groups have
been updated to "Normal" (01).
(Perform this when no other errors have
occurred.
In addition, other errors may occur when
there is a communication error, however,
in this checking step, attention should be
focused on error codes).
(1) From the building management system,
change the operational mode for a specific
group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the operational
*4
mode for the relevant group is updated to
*5
the operating mode.
43