Trend log specifications (only for portions related to the apportioned electricity billing function)
Item
Collection cycle
Collection period
Collection timing
Collection starts
Log deleted
*1 When the collection cycle is 30 minutes
*2 When the collection cycle is 1 day
5-5-2. Accumulator object
The instance number of the accumulator object which stores the cumulative value is as follows.
Object
Group Apportioned
Electric Energy
Interlocked Units
Apportioned Electric
Energy
PIcontroller Electric
Energy 1–4
Pulse Input Electric
Energy 1–4
Group Apportionment
Parameter
Interlocked Units
Apportionment
Parameter
* xx: Group number (01–50)
* mm: PI controller address (01–50)
* aa: Interlocked unit address (01–50)
WT07919X04
Setting contents
30 minutes to 1440 minutes (1 day)
Can be set in 30-minute increments.
("Log_Interval" property)
Initial value: 30 minutes
4 days
*1
to 192 days
*2
(retain the value for the most recent 192 items)
Carry out collection for each collection cycle using 1970/1/1
00:00:00 as a starting point.
After participation sequence completed (Status = Operational)
When "0" is written to the "Record_Count" property
Object
Instance
type
number
AC
01xx39
AC
61aa39
AC
41mm40–43
Apportionment
AC
410040–43
AC
01xx44
Apportionment
AC
61aa44
Apportioning
Metering
type
device
Apportioned
results
Required
source data
Not
parameter
required
27
Setting method
Settings on the building
management system
Contents
Stores the cumulative value of the electric
energy (indoor unit + outdoor unit) for each
group.
Stores the cumulative value of the electric
energy (indoor unit + outdoor unit) for each
interlocked unit (OA Processing Unit).
Cumulative value (for 4 channels) of
electric energy accumulated in PI controller
Cumulative value (for 4 channels) of
electric energy accumulated in a built-in
Pulse Input (PI) of AE-50/EW-50
Stores electric energy apportionment
parameters (for outdoor units) for each
group.
Stores electric energy apportionment
parameters (for outdoor units) for each
interlocked unit (OA Processing Unit).