Chapter 2 Parameter Settings; Parameter Setting Procedure; Basic Setting - Mitsubishi Electric RD62P2E Application User's Manual

High-speed counter module
Table of Contents

Advertisement

2
PARAMETER SETTINGS
This chapter describes the parameter settings of the high-speed counter module. Setting parameters here eliminates the
need to program them.
2.1

Parameter Setting Procedure

1.
Add the high-speed counter module to an engineering tool.
Navigation window  [Parameter]  [Module Information]  Right-click  [Add New Module]
2.
The basic setting, application setting, interrupt setting, and refresh settings are included in the parameter setting. Select
one of the settings from the tree on the window shown below.
Navigation window  [Parameter]  [Module Information]  Select the high-speed counter module  [Module
Parameter]
3.
Write the setting to the CPU module with an engineering tool.
[Online]  [Write to PLC]
4.
When the CPU module is reset or is powered off and on, the setting is reflected.
2.2

Basic Setting

Set the parameters for the basic functions of the high-speed counter module.
Item
*1
Pulse input mode
*1
Counting speed setting
*1
Counter type
Setting range
• 0: 1-phase multiple of 1 (default value)
• 1: 1-phase multiple of 2
• 2: CW/CCW
• 3: 2-phase multiple of 1
• 4: 2-phase multiple of 2
• 5: 2-phase multiple of 4
• 0: 10kpps (default value)
• 1: 100kpps
• 2: 200kpps
• 3: 500kpps (RD62D2 only)
• 4: 1Mpps (RD62D2 only)
• 5: 2Mpps (RD62D2 only)
• 6: 4Mpps (RD62D2 only)
• 7: 8Mpps (RD62D2 only)
• 0: Linear counter (default value)
• 1: Ring counter
Reference
2 PARAMETER SETTINGS
2.1 Parameter Setting Procedure
2
39