2.3

Application Setting

Set the parameters for the various functions of the high-speed counter module.
Item
Counter function selection setting
Sampling/cycle time setting
Function input response time setting
*1
Preset input response time setting
Pulse measurement section setting
PWM output cycle time setting
PWM output ON time setting 1
PWM output ON time setting 2
*1*2
CPU error output mode setting
*1 The item can be set only in the parameter setting. It cannot be changed from the program.
*2 The external output status (clear/hold) of the high-speed counter module for when a CPU stop error occurs can be set.
*3 If a value larger than 1Mpps is set in "Counting speed setting" when the RD62D2 is used, the unit is changed from 10ms to 1ms.
Setting range
• 0: Count disable function (default value)
• 1: Latch counter function
• 2: Sampling counter function
• 3: Cycle pulse counter function
1 to 65535 (default value: 0)  10ms
*1
• 0: Response time 0ms
• 4: Response time 0.1ms (default value)
• 8: Response time 1ms
• 10: Response time 10ms
• 0: Response time 0ms
• 4: Response time 0.1ms (default value)
• 8: Response time 1ms
• 10: Response time 10ms
• 0: ON width (default value)
• 1: OFF width
• 2: RiseRise
• 3: FallFall
0 to 2147483647 (default value: 2147483647) 
0.1s
0 to 2147483647 (default value: 0)  0.1s
0 to 2147483647 (default value: 0)  0.1s
• 0: Clear (default value)
• 1: Hold
Reference
Page 63 CH1 Counter function selection setting
*3
Page 63 CH1 Sampling/cycle time setting
Page 67 CH1 Pulse measurement section setting
Page 67 CH1 PWM output cycle time setting
Page 67 CH1 PWM output ON time setting 1
Page 67 CH1 PWM output ON time setting 2
2 PARAMETER SETTINGS
2.3 Application Setting
2
41