Pulse Measurement Function - Mitsubishi Electric RD62P2E Application User's Manual

High-speed counter module
Table of Contents

Advertisement

1.6

Pulse Measurement Function

This mode measures the following times of the pulse input in the function start input terminal.
• ON width
• OFF width
• From the rising edge of the pulse to the rising edge of the next pulse
• From the falling edge of the pulse to the falling edge of the next pulse
When the next pulse is measured, the measured value is written over the previous value.
Function start input terminal
Setting method of the pulse measurement function
To use the pulse measurement function, select "Pulse measurement mode" for "Counter operation mode" in the parameter
settings.
Navigation window  [Parameter]  [Module Information]  Module model name  [Module Parameter]  [Basic
setting]
Terminals for the pulse measurement function
This function measures the pulse input in the function start input terminal.
Measurement target
Set the measurement target by storing a value in CH1 Pulse measurement section setting (Un\G512).
On width
Off width
Measurement target
ON width
OFF width
From the rising edge of the pulse to the rising edge of the next pulse
From the falling edge of the pulse to the falling edge of the next pulse
Starting and stopping methods of the pulse measurement
The start or stop of the pulse measurement is determined by CH1 Pulse measurement start command (pulse measurement)
(Y6). The pulse measurement starts at the rising edge of the signal and stops at the falling edge of the signal.
1 FUNCTIONS
34
1.6 Pulse Measurement Function
High-speed counter
module
Analysis
Pulses
Rising edge to rising edge
Falling edge to falling edge
Buffer memory
CH1 Measured pulse value
(Un\G516 to Un\G517)
Setting value in CH1 Pulse measurement section setting
(Un\G512)
0
1
2
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd62d2Melsec iq-r seriesRd62p2

Table of Contents