1.8
Shift Function
This function adds the set input value shift amount to the digital input value.
The analog output value reflects the change in the input value shift amount on a realtime basis. Therefore, fine adjustment
can be easily performed when the system starts.
Operation
When the D/A conversion is performed on the digital value, the value obtained by adding 'CH1 Input value shift amount'
(Un\G480) to 'CH1 Digital value' (Un\G460) is used for the D/A conversion.
When the digital value after the addition exceeds the range of -32768 to 32767 as the result of the shift processing, the value
is fixed with the lower limit value (-32768) or the upper limit value (32767).
When a value is written to 'CH1 Input value shift amount' (Un\G480), the set value is added to the digital input value
regardless of the ON/OFF state of 'Operating condition setting request' (Y9).
Setting procedure
Set the shift amount to "Input value shift amount".
Navigation window [Parameter] [Module Information] Module name [Module parameter] "Application
setting" "Shift function"
Item
Input value shift amount
Setting example
Ex.
When the output range is 0 to 5V and the input value shift amount is +50
Analog output voltage (V)
5
Before
adjustment
0
adjustment
-50
0
Digital value
Before adjustment
-50
31950
1 FUNCTIONS
26
1.8 Shift Function
Input value
shift
After
digital value
32000
31950
After adjustment
0
32000
Setting range
-32768 to 32767
Analog output voltage (V)
0
5