Checking Vxworks Image File - Mitsubishi Electric MELSEC iQ-R Series User Manual

Controller module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

6.11

Checking VxWorks Image File

Before debugging a user program, check that the VxWorks image file version in the personal computer and a C Controller
module is the same.
Specifying a different version of VxWorks image file prevents normal debugging.
(2)
(1)
(1) VxWorks image file
(2) Same version
Checking method
The checking methods for the VxWorks image file are shown below.
■C Controller module
Check the firmware version with the diagnostic function of CW Configurator or the rating plate on the side of the C Controller
module.
■Personal computer
Check the file name of VxWorks image file specified with CW Workbench.
*1
• R12CCPU-V_XX
*1 XX: Firmware version
Version of VxWorks image files are not identical
If the version of VxWorks image file is different, acquire the new image file stored in the C Controller module.
1.
Connect the C Controller module with the personal computer. (Page 23 WIRING)
2.
Acquire the VxWorks image file
*1 The file is stored in the system memory (/SYSTEMROM/OS_IMAGEFILE).
3.
Reconfigure the target server setting with CW Workbench.
The default settings of the FTP function are as follows:
• Login name: target
• Password: password
(1)
*1
in the C Controller module using the FTP function.
6 PROCEDURE BEFORE OPERATION
6.11 Checking VxWorks Image File
6
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

R12ccpu-v

Table of Contents