1MRK 511 440-UEN A
Section 6
6.1
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual
Data sets and control blocks

Data sets

IEC 61850 has defined data sets and report control blocks to transmit signals for
monitoring purposes. Data sets are also used for GOOSE messages in horizontal
communication among IEDs. The project defines the data objects or single data
attributes that should be collected in a data set. Figure
position information of the apparatuses of a bay are put into one data set.
PCM600 will generate default data sets, based on the current ACT configuration.
The default data sets can be modified or removed in the engineering tools. No
RCBs are created automatically by PCM600. However, the configured IEDs are
delivered with RCBs for all default data sets or when templates are used.
LD0
LLN0
LPHD
SXCBR1
SCSWI1
SXSWI1
SCSWI2
SXSWI2
SCSWI3
SXSWI3
SCSWI4
SXSWI4
SCSWI5
IEC17000140 V1 EN-US
Figure 8:
IEC 61850–7–2: Example of a data set for MMS
General rules for data set configuration:
Data sets and control blocks
8
shows a data set where all
LD0/LLN0.AppPos
LD0/SXCBR1.Pos FC=ST
LD0/SXSWI1.Pos FC=ST
Pos
LD0/SXSWI2.Pos FC=ST
LD0/SXSWI3.Pos FC=ST
Pos
LD0/SXSWI4.Pos FC=ST
Pos
Pos
stVal
Pos
Origin
Section 6
SEMOD129786-5 v9
DATA-SET
q
t
IEC17000140-1-en.vsd
27