1MRK 511 440-UEN A
DO name
DO type
AccAPwr
v2_dMV
PresAlm
v3_dSPS
OpCnt
v5_dINS
7.8.2
7.8.2.1
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual
DA name
FC
q
MX
t
MX
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
Since there is no current measurement functionality in SAM600-IO,
evaluation of the following parameters are not possible in the
circuit breaker condition monitoring function (SSCBR):
•
Circuit breaker status
•
Remaining life of the circuit breaker
•
Contact erosion estimation
•
Circuit breaker contact travel time
Setting parameters AccmPwrAlm, AccmPwrLo, CBLifeAlm,
RmnNumOp, ClsAlm, OpnAlm, AccmAPwr, RsAccmAPwr,
RsRmnNumOp, andRsTrvTm are not available in SAM600-IO.
Insulation medium supervision (gas) SIMG
Gas medium supervision SSIMG
LN type
LN prefix LN class Function block name
SSIMG (revision 0) S
T
Signal
-
IPOWPH
-
IPOWPH
-
GPRESALM
-
GPRESALM
-
GPRESALM
-
NOOPER
-
NOOPER
-
NOOPER
SIMG
SSIMG
Section 7
Logical node data model
Mon/C
Description
md
Mon
Quality: Accumulated
I^CurrExponent integrated over
CB open travel time
Mon
Timestamp: Accumulated
I^CurrExponent integrated over
CB open travel time
Mon
Pressure below alarm level
Mon
Quality: Pressure below alarm
level
Mon
Timestamp: Pressure below
alarm level
Mon
Number of CB operation cycle
Mon
Quality: Number of CB operation
cycle
Mon
Timestamp: Number of CB
operation cycle
GUID-B3D47A00-E233-4E54-910F-97BCD32C501A v1
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
PID-3703-LOGICALNODEDATA v3
73