Insulation Medium Supervision (Gas) Simg; Gas Medium Supervision Ssimg - ABB SAM600-IO Protocol Manual

Switchgear control unit
Hide thumbs Also See for SAM600-IO:
Table of Contents

Advertisement

1MRK 511 440-UEN A
DO name
DO type
AccAPwr
v2_dMV
PresAlm
v3_dSPS
OpCnt
v5_dINS
7.8.2
7.8.2.1
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual
DA name
FC
q
MX
t
MX
stVal
ST
q
ST
t
ST
stVal
ST
q
ST
t
ST
Since there is no current measurement functionality in SAM600-IO,
evaluation of the following parameters are not possible in the
circuit breaker condition monitoring function (SSCBR):
Circuit breaker status
Remaining life of the circuit breaker
Contact erosion estimation
Circuit breaker contact travel time
Setting parameters AccmPwrAlm, AccmPwrLo, CBLifeAlm,
RmnNumOp, ClsAlm, OpnAlm, AccmAPwr, RsAccmAPwr,
RsRmnNumOp, andRsTrvTm are not available in SAM600-IO.

Insulation medium supervision (gas) SIMG

Gas medium supervision SSIMG

LN type
LN prefix LN class Function block name
SSIMG (revision 0) S
T
Signal
-
IPOWPH
-
IPOWPH
-
GPRESALM
-
GPRESALM
-
GPRESALM
-
NOOPER
-
NOOPER
-
NOOPER
SIMG
SSIMG
Section 7
Logical node data model
Mon/C
Description
md
Mon
Quality: Accumulated
I^CurrExponent integrated over
CB open travel time
Mon
Timestamp: Accumulated
I^CurrExponent integrated over
CB open travel time
Mon
Pressure below alarm level
Mon
Quality: Pressure below alarm
level
Mon
Timestamp: Pressure below
alarm level
Mon
Number of CB operation cycle
Mon
Quality: Number of CB operation
cycle
Mon
Timestamp: Number of CB
operation cycle
GUID-B3D47A00-E233-4E54-910F-97BCD32C501A v1
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
PID-3703-LOGICALNODEDATA v3
73

Advertisement