Section 6
Data sets and control blocks
30
Link BRCB to a client LN
The BRCB has to know to whom the events shall be transmitted. This is the signal
routing engineering step. The IEC standard 61850–6 describes that this is given by
including the LN of the client IED in the ReportBlockEnabled option.
The selected client IED with the corresponding LN, for example, ITCI is included
in the SCL structure of the Report Control description of the IED section.
The description of the BRCB with selected DataSet, configured parameters and
selected IEDs is included in the SCL file in the IED section in the LN0 structure
for the LD where this LN0 belongs to.
IED
HSI
Client 1
IHSI1
Server 1
LLN0
IED 1
IEC06000107 V2 EN-US
Figure 9:
Link BRCB to a client LN
Note that the possible trigger options for each attribute
are included and defined in the datatype template section
in SCL.
IED
NCC GW 1
Client 2
ITCI1
Subnetwork
DATA-SET
LD0/LLN0.AppPos
LD0/SXCBR1.Pos FC=ST
LD0/SXSWI1.Pos FC=ST
LD0/SXSWI2.Pos FC=ST
LD0/SXSWI3.Pos FC=ST
LD0/SXSWI4.Pos FC=ST
Switchgear control unit SAM600-IO Version 2.2 IEC
1MRK 511 440-UEN A
IED
NCC GW m
Client m
ITCI2
en06000107.vsd
Communication protocol manual